Click the ON/OFF radio box to set the Safe value and then click the button
to enable the settings to take effect.
C.4. AI High/Low Alarm
ET-7017/PET-7017 and ET-7017-10 module equip with the High/Low Alarm function.
When the alarm function is enabled, the specified registers are the alarm indicator.
The alarm function is to compare the analog input value with given high alarm value
and low alarm value.
Address 00636 to 00667 can be used to enable/disable the AI High Alarm function.
Address 00668 to 00699 can be used enable/disable the AI Low Alarm function.
ET-7017/PET-7017 AI High/Low Alarm Switch Table
Channel
Number
AI High Alarm
AI Low Alarm
Register
Description
Register
Description
AI0
00636
0: Disable/1: Enable
00668
0: Disable/1: Enable
AI1
00637
0: Disable/1: Enable
00669
0: Disable/1: Enable
AI2
00638
0: Disable/1: Enable
00670
0: Disable/1: Enable
AI3
00639
0: Disable/1: Enable
00671
0: Disable/1: Enable
AI4
00640
0: Disable/1: Enable
00672
0: Disable/1: Enable
AI5
00641
0: Disable/1: Enable
00673
0: Disable/1: Enable
AI6
00642
0: Disable/1: Enable
00674
0: Disable/1: Enable
AI7
00643
0: Disable/1: Enable
00675
0: Disable/1: Enable
AI8
00644
0: Disable/1: Enable
00676
0: Disable/1: Enable
AI9
00645
0: Disable/1: Enable
00677
0: Disable/1: Enable