Savin P7026 Manual do Utilizador Página 76

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 75
PET-70216/ET-7026 User Manual, version 1.0.1 beta1, Page: 76
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]om
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
of the previous AI values
of one channel for all AI
1 = enable
(Default = 0)
348
1
Enable Average of all
enabled channel,
High/Low Alarm value of
all AI average value and
Average latched values for
all AI channels
1
0 = disable
1 = enable
(Default = 0)
R/W/E
349
1
Save Module Nick Name
to EEPROM
1
1 = write
W/E
(Pulse)
350
1
Enable all DI latch latched
status (high/low)
1
0 = disable
1 = enable
(Default = 0)
R/W/E
351
0 ~ 15
Enable low speed (100Hz)
digital counter
1
0 = disable
1 = enable
(Default = 0)
R/W/E
365 ~
427
Reserved
429
1
DI inverse enable
1
0 = disable
1 = enable
(Default = 0)
R/W/E
430
1
DO inverse enable
1
0 = disable
1 = enable
(Default = 0)
R/W/E
431
1
Write DO Power on value
to EEPROM
1
1 = write
W
(Pulse)
432
1
Write DO Safe value to
EEPROM
1
1 = write
W
(Pulse)
435
0 ~ 79
(80)
Power on value for DO
1
0 = off
1 = on
(Default = 0)
R/W/E
515
0 ~ 79
(80)
Safe value for DO
1
0 = off
1 = on
(Default = 0)
R/W/E
595
0 ~ 31
(32)
Enable/Disable AI channel
1
0 = disabled
1 = enabled
R/W/E