4.3. Modbus Register Map
4.3.1. Read/Write Coils (0xxxx)
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
0
0 ~ 31
(32)
Digital Out
1
0 = off
1 = on
R/W
32
1
Clear all DI latched High
1
1 = clear
W
(Pulse)
33
1
Clear all DI latched Low
1
1 = clear
W
(Pulse)
34
0 ~ 15
(16)
Clear low speed (100 Hz)
Digital Counter (single)
1
1 = clear
W
(Pulse)
49 ~ 97
Reserved
98
0 ~ 31
Clear DI Latch High
(single)
1
1 = clear
W
(Pulse)
130
0 ~ 31
Clear DI Latch Low
(single)
1
1 = clear
W
(Pulse)
162
0 ~ 31
Clear AI latch High (single)
1
1 = clear
W
(Pulse)
194
0 ~ 31
Clear AI latch Low (single)
1
1 = clear
W
(Pulse)
210 ~
225
16
Reserved
226
1
Recover all I/O default
settings
1
1 = clear
W
(Pulse)
233
1
Reboot
PET-7000/ET-7000
1
1 = reboot
W
(Pulse)
250
0 ~ 89
(90)
DO mapping address for
external Modbus devices
1
0 = off
1 = on
R/W
340 ~
346
7
Reserved
347
1
Enable the average value
1
0 = disable
R/W/E