PET-70216/ET-7026 User Manual, version 1.0.1 beta1, Page: 77
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]om
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
(Default = 1)
628
1
Normal/Fast mode for AI
1
0 = normal (16
bit)
1 = fast (12 bit)
(Default = 0)
R/W/E
629
1
50/60 Hz rejection for AI
1
1 = 50 Hz
0 = 60 Hz
(Default = 0)
R/W/E
630
1
Write DI counter preset
value to EEPROM
1
1 = write
W
(Pulse)
631
1
AI data format
1
1 = engineering
0 = hex
(Default = 0)
R/W/E
632
1
Return the factory
calibration (ALL)
1
1 = clear
R/ W
(Pulse)
633
Reserved
634
1
Clear AI Latch High (ALL)
1
1 = Clear
W
(Pulse)
635
1
Clear AI Latch Low (ALL)
1
1 = Clear
W
(Pulse)
636
0 ~ 31
(32)
AI Alarm High Switch
1
0 = Disabled
1 = Enabled
R/W/E
668
0 ~ 31
(32)
AI Alarm Low Switch
1
0 = Disabled
1 = Enabled
R/W/E
700
0 ~ 31
(32)
AI Alarm High Mode
1
0 = Moment
1 = Latched
R/W/E
732
0 ~ 31
(32)
AI Alarm Low Mode
1
0 = Moment
1 = Latched
R/W/E
764
0 ~ 31
(32)
AI Alarm High
1
0 = OK
1 = alarm
(Clear)
R/W
(Pulse)
796
0 ~ 31
(32)
AI Alarm Low
1
0 = OK
1 = alarm
(Clear)
R/W
(Pulse)
828
1
High Alarm of Average
value of all AI channel
1
0 = OK
1 = alarm
R/W
(Pulse)