Installation and Operating Instructions
SDC 306 1316BED036-11B-E Date 06/09
- 26 -
10
C
ONTROLLER FUNCTIONS
The SDC 306 controllers include
comprehensive functions for controlling and
monitoring the solar thermal system. A
basic distinction is made between:
• Control functions for loading the storage
cylinder
• Functions for system protection and
system monitoring
• Additional functions
10.1 General control functions
The control unit records the temperatures
from the various measuring points and
calculates the correct time to load the
storage cylinders, based on the
programmed (additional) functions and
control parameters.
To
prevent the pump from switching on and
off due to only minimal differences in
temperature, a switch-on hysteresis, e.g. 7K
and switch-off hysteresis, e.g. 3K is preset
.
.
10.1.1 Load storage cylinder
Relevant values in menu
“Program”
Maximum temperature
Td start
Switch-on temperature difference
Td stop
Switch-off temperature difference
The storage cylinder is loaded to the
specified maximum temperature via the
pump on output A1, provided the collector
temperature is a certain amount higher than
that of the storage cylinder temperature.
The switching behaviour can be set via Td
start and Td stop, whereby the value for Td
start cannot be lower than that for Td stop +
1. To prevent the pump from switching on
and off due to only minimal differences in
temperature, a hysteresis of 5K is preset as
the storage cylinder maximum temperature.
Load cylinder
(base of cylinder
Max
65 °C
T[°C]
Pump on
(A1)
On
Off
TColl
TSt
dT start
dT stop