Installation and Operating Instructions
SDC 306 1316BED036-11B-E Date 06/09
- 37 -
11.6 Basic system diagram 6:
1 collector array, 1 storage cylinder, auxiliary heating, return line temperature increase
System 6 has one collector surface, one
storage cylinder, one auxiliary heating
function (thermostat, timeframe) and one
return line temperature increase. The
control unit controls the solar function
(temperature difference regulation), the
auxiliary heating (thermostat, timeframe)
and the return line temperature increase
(temperature difference regulation). Heat
metering is also possible, e.g. using an
impeller flow meter.
Info Program Manual operation Basic setting
I I I I
Current collector temperature (E1) Timeframe R2 start Pump A1 off/on Code entry
Minimum collector temperature (E1) Timeframe R2 stop A2 off/on Reset/factory setting
Maximum collector temperature (E1) Maximum temperature of
storage cylinder
A3 off/on Select basic
configuration
Current storage temp. at bottom (E2) Solar circuit Td start A4 off/on Max. collector temp.
Minimum storage temp. - bottom (E2) Solar circuit Td stop Mode yield metering
Maximum storage cylinder
temperature at bottom (E2)
Start temperature, auxiliary
heating
Volume flow
∗
Current storage temp. at top (E3) R3 Td start
DFG/WMM
∗∗
Minimum storage temp. at top (E3) R3 Td stop
Glycol type
∗
Maximum storage temp. at top (E3) Set time
Glycol percentage
∗
Current storage temp. at centre (E4) Tolerance for solar yield
Minimum storage cylinder temperature
at centre (E4)
Maximum temperature
for return line
Maximum storage cylinder
temperature at centre (E4)
Code change
Current return line temperature (E5)
Minimum return line temperature (E5)
Maximum return line temperature (E5)
Flow rate
∗
Daily yield
∗
Total yield
∗
∗ Displayed only if yield metering mode is equivalent to 1 or 2.
∗∗ Displayed only if yield metering mode is equivalent to 2.