Installation and Operating Instructions
SDC 306 1316BED036-11B-E Date 06/09
- 27 -
10.1.2 Yield estimation / yield metering
For the purposes of yield estimation (heat
quantity), the collector sensor serves as a
reference sensor for the hot flow, the
storage cylinder sensor at the bottom
serves as a reference sensor for the cool
return line. The volume flow, type of glycol
and glycol concentration are entered in the
control unit. A daily yield value is calculated
from these five values and can be
displayed. Adding together the daily yields,
in each case at 0:00 gives the total amount
which can also be displayed. The yields can
be reset manually.
For the purposes of yield metering, instead
of entering a volume flow, the value
measured by a flow meter is processed as
volume flow.
10.1.3 Password
The parameters contained in the “Basic
settings” menu can be changed only
following entry of a 4-digit numerical
password. Once the password has been
entered, it can also be changed.
10.1.4 Auxiliary heating
For the upper part of the storage cylinder
(standby capacity), a start temperature for
auxiliary heating is preset. Once the
temperature of the water reaches this
temperature, the auxiliary heating is
triggered so that the water cannot fall below
this temperature. A clock timer is available
for this function.
To prevent the pump from switching on and
off due to only minimal differences in
temperature, a hysteresis of 5K is preset.
10.1.5 Tolerance for solar yield
In the case of a solar yield from the
collector, the “Start temperature for auxiliary
heating” (minimum temperature) is reduced
by the amount set for “Tolerance for solar
yield”. In other words, if loading takes place
between the collector array and the storage
cylinder, the auxiliary heating is triggered to
reach a reduced value (e.g. 60°C 10K =
50°C). If no loading takes place for at least
15 minutes, the reduction is removed again.
This allows the solar thermal system to
provide higher yields.
10.1.6 Increase in return line temperature
In the case of solar thermal systems with
auxiliary heating, the solar energy from the
storage cylinder can be used via a
temperature increase in the boiler return. If
there is a difference in temperature between
the return line of the heating circuit and the
base/centre of the solar storage cylinder, a
3-way valve is activated so that the lower
part of the combination storage cylinder
runs in series to the heating return line.
To prevent the pump from switching on and
off due to only minimal differences in
temperature, a hysteresis is preset.